EasyManua.ls Logo

Siemens SENTRON PAC5200 - Page 29

Siemens SENTRON PAC5200
266 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 Measurands and Recording
4.1 Measuring and Recording System
29SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
Overvoltage of the Mains Voltage
The basic measurement of the RMS value V
rms
of overvoltage is the determination of the RMS value
V
rms
(1/2) for each single measuring channel. The limiting value for overvoltages is a percentage value of
Udin.
The factory setting of the hysteresis is 2 % of Udin. It can be set from 1 % to 6 %.
In multi-phase systems, all channels are independently synchronized in the zero point of the voltage.
In 1-phase systems, overvoltage begins when the voltage V
rms
rises above the threshold of the
overvoltage. Overvoltage ends when the voltage V
rms
falls below the threshold value of the overvoltage
minus the hysteresis.
In multi-phase systems, overvoltage begins when the voltage V
rms
rises above the threshold of the
overvoltage in one or more channels. Overvoltage ends when the voltage V
rms
falls below the threshold
value of the overvoltage minus the hysteresis in all measured channels.
The overvoltage threshold value and the hysteresis were parameterized according to the measuring task.
Overvoltage is characterized by the data pair Maximum value of overvoltage and duration (t):
The maximum value of an overvoltage is the highest voltage value of V
rms
which is measured in a channel
during overvoltage.
Voltage Interruption
In 1-phase systems, a voltage interruption begins when the voltage V
rms
falls below the threshold of the
voltage interruption. The voltage interruption ends when the voltage V
rms
rises above the threshold value
of the voltage interruption plus the hysteresis.
In multi-phase systems, the voltage interruption begins when the voltages V
rms
fall below the threshold of
the voltage interruption in all channels. The voltage interruption ends when the voltage V
rms
rises above
the threshold value of the voltage interruption plus the hysteresis in any of the measured channels.
The voltage interruption threshold value and the hysteresis are parameterized according to the measuring
task.
The factory setting of the hysteresis is 2 % of Udin. It can be set from 1 % to 6 %.
Unbalance of the Mains Voltage
The mains voltage unbalance is determined using the method of the symmetrical components. In case of
unbalance, the negative-sequence component U
2
is determined in addition to the positive-sequence
component U
1
. The fundamental component of the voltage is measured over a 10-period time interval for
50-Hz distribution systems and over a 12-period time interval for 60-Hz distribution systems.
Harmonics of the Mains Voltage
interruption-free 10-/12-period measurement of a harmonics subgroup U
sg,n
according to
IEC 61000-4-7.
The total distortion is calculated as the subgroup total harmonic distortion (THDS) according to IEC 61000-
4-7.
Measurements are performed up to the 40th harmonics order.

Table of Contents

Related product manuals