4 Measurands and Recording
4.1 Measuring and Recording System
28 SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
Definition of the Measurands
Mains Voltage Level
The measurement determines the RMS value of the mains voltage over a 10-period time interval for 50-
Hz distribution systems and over a 12-period time interval for 60-Hz distribution systems. All 10-/12-period
time intervals are measured without interruption and overlapping (the overlapping area excluded, see
Figure 4-1).
Undervoltage of the Mains Voltage
The basic measurement of the RMS value V
rms
of an undervoltage is the determination of the RMS value
V
rms
(1/2) for each single measuring channel (see Figure 4-2). The limiting value for undervoltages is a
percentage value of Udin.
The factory setting of the hysteresis is 2 % of Udin. It can be set from 1 % to 6 %.
In multi-phase systems, all channels are independently synchronized in the zero point of the voltage.
In 1-phase systems, undervoltage begins when the voltage V
rms
falls below the threshold of the
undervoltage. Undervoltage ends when the voltage V
rms
rises above the threshold value of the
undervoltage plus the hysteresis.
In multi-phase systems, undervoltage begins when the voltage V
rms
falls below the threshold of the
undervoltage in one or more channels. Undervoltage ends when the voltage V
rms
rises above the
threshold value of the undervoltage plus the hysteresis in all measured channels.
The undervoltage threshold value and the hysteresis are parameterized according to the measuring task.
Undervoltage is characterized by the data pair residual voltage (V
res
) and duration (t):
The residual voltage is the smallest voltage value of V
rms
which is measured in a channel during
undervoltage.
Figure 4-2 Undervoltage Representation
-70
-60
-50
-40
-30
-20
-10
0
10
20
30
40
50
60
70
V [V]
44,85 44,90 44,95
t [s]
V
rms
(1/2) :
RMS value over one period synchronized to the zero point of the fundamental
component , updated after each half period .
This value is only used to detect undervoltages , overvoltages and voltage
interruptions.
V
rms
n
n+1
n+2
n+3
n+4
n+5
n+6
n+7
n+8
n+ 9
n+10
V
rms
V
rms
V
rms
V
rms
V
rms
V
rms
V
rms
V
rms
V
rms
V
rms