Service and maintenance
13.2 Error messages
SIMATIC RF600
Configuration Manual, 11/2018, C79000-G8976-C386-07
255
AutoId
status
XML/
LED
(hex)
OPC UA
status
AutoId
text
Error description
19 0x93 good RF_COMMUNICATION_
ERROR
The verification of the written transponder data has failed.
19 0x94 good RF_COMMUNICATION_
ERROR
General transponder error
19 0x95 good RF_COMMUNICATION_
ERROR
The transponder has too little power to execute the com-
mand.
19 0xA3 good RF_COMMUNICATION_
ERROR
The transponder signals a CRC error.
19 0xA5 good RF_COMMUNICATION_
ERROR
The selected frequency is not enabled.
19 0xA6 good RF_COMMUNICATION_
ERROR
The carrier signal is not activated.
19 0xA8 good RF_COMMUNICATION_
ERROR
General radio protocol error
20 0x41 good DEVICE_FAULT Fault in power supply
The power supply is very close to the low limit.
20 0x43 good DEVICE_FAULT Antenna error
The antenna or the antenna cable is defective.
Error in the connection to the reader; the reader is not
answering (in PROFIBUS operation).
The cable between the communications module
and reader is wired incorrectly or there is a cable
break
The 24 V supply voltage is not connected or is
turned off or has failed briefly
Automatic fuse on the communications module
has blown
Hardware defective
Another reader is in the vicinity and is active
There is a reflecting metal surface in the vicinity
that is disrupting the antenna field
Execute "init_run" after correcting the error
--
0xA4
--
--
The selected antenna is not enabled.
-- 0x46 OpcUa_
BadInva-
lidState
-- The command is not permitted in this status or is not
supported.
Possible cause:
"INIT" was chained.
Command repetition was started without "Presence
mode".