L+
Technical Specifications
Number of outputs 8
Galvanic isolation yes (optocoupler)
- in groups of 8
Load voltage L+
- rated value 24 V DC
- permissible range 20 to 30 V
(including ripple)
- value at t<0.5 s 35 V
Output current for
"1" signal
- rated value 1 A
- permissible range 5 mA to 1A
- lamp load max. 10 W
Residual current at
"0" signal max. 0.5 mA
Output voltage
- at "1" signal max. L+ (- 0.6 V)
Short-circuit protection short-circuit protected
output with autom.
switch
Fault LED (red) short-circuit
Voltage induced on
circuit interruption
(internal) limited to -15 V
Switching frequency
- resistive load max. 100 Hz
- inductive load max. 2 Hz
Permissible current
of all outputs 6 A
Driving of digital input possible
Paralleling of 2 outputs possible in pairs
- maximum current 1.8 A
Length of cable
- unshielded max. 100 m (330 ft.)
Rated insulation voltage
(+ 9 V to L+) 24 V AC
- insulation group 2 x B
- tested with 500 V AC
Rated insulation voltage
(+ 9 V to ) 12 V AC
- insulation group 1 x B
- tested with 500 V AC
Current consumption
- from +9 V (CPU) typ. 35 mA
- from L+ (without load) typ. 50 mA
Power loss
of the module typ. 3 W
Weight approx. 230 g (8 oz.)
EMC Characteristics for Use in S5-95F
Electrostatic discharge
to IEC 801-2 Severity rating 3
tested with 8 kV air discharge
6 kV contact discharge
Electromagnetic fields
to IEC 801-3 Severity rating 2
tested with 3 V / m
Fast transient burst
to IEC 801-4 Severity rating 2
tested with 1.5 kV on supply lines
1 kV on signal lines