X.2
Technical Specifications
Number of outputs 8
Galvanic isolation yes (optocoupler)
- in groups of 8
Load voltage L1
- rated value 115 to 230 V AC
- frequency max. 47 to 63 Hz
- permissible range 85 to 264 V
Output current for
”1” signal
- rated value 0.5 A
- permissible range 50 mA to 0.5 A
- lamp load max. 25/50 W
Contact current
closing rating: determined by the size
of the fuse
Residual current at
”0” signal max. 3/5 mA
Output voltage
- at ”1” signal max. L1 (-7 V)
Signal Status Display only with load
(green LEDs) connected
Short-circuit protection fuse (10 A extra fast)
(Wickmann No. 19231
or 6ESS5 980-3BC41)
Switching frequency max. 10 Hz
Permissible current
of all outputs 4 A
Driving of digital input possible
Paralleling of outputs not possible
Length of cable
- unshielded max. 100 m (330 ft.)
Rated insulation voltage
(+9 V to L1) 250 V AC
- insulation group 2×B
- tested with 1500 V AC
Rated insulation voltage
(+9 V to ) 12 V AC
- insulation group 1×B
- tested with 500 V AC
Current consumption
- from +9 V (CPU) typ. 25 mA
Power loss of the
module typ. 3.5 W
Weight approx. 270 g (9 oz.)
EMC Characteristics for Use in S5-95F
Electrostatic discharge
to IEC 801-2 Severity rating 3
tested with 8 kV air discharge
6 kV contact discharge
Electromagnetic fields
to IEC 801-3 Severity rating 2
tested with 3 V / m
Fast transient burst
to IEC 801-4 Severity rating 2
tested with 1.2 kV on supply lines
1 kV on signal lines