Technical Specifications
Outputs 4 relay outputs, contact
switching varistor
Galvanic isolation yes (optocoupler)
- in groups of 1
Continuous current I
th
5 A
Length of cable
- unshielded max. 100 m (330 ft.)
Rated insulation voltage
(+ 9 V to L 1) 250 V AC
- insulation group 2 x B
- tested with 1500 V AC
Rated insulation voltage
(+ 9 V to ) 12 V AC
- insulation group 1 x B
- tested with 500 V AC
Current consumption
- from + 9 V (CPU) typ. 14 mA
- from L+ typ. 100 mA
Power loss
of the module typ. 2 W
Weight approx. 240 g (8 oz.)
Switching capacity
of the contacts
- resistive load max. 5 A at 250 V AC
2.5 A at 30 V DC
- inductive load max. 1.5 A at 250 V AC
0.5 A at 30 V DC
Operating cycles of
the contacts according to
VDE 0660, part 200
- AC - 11 1.5 x 10
6
- DC - 11 0.5 x 10
6
Switching frequency max. 10 Hz
Rated insulation voltage
(between contacts) 250 V AC
- insulation group 2 x B
- tested with 1500 V AC
Supply voltage L+
(for the relays)
- rated value 24 V DC
- ripple V
PP
max. 3.6 V
- permissible range
(ripple included) 20 to 30 V
- value at t <0.5 s 35 V
EMC Characteristics for Use in S5-95F
Electrostatic discharge
to IEC 801-2 Severity rating 3
tested with 8 kV air discharge
6 kV contact
discharge
Electromagnetic fields
to IEC 801-3 Severity rating 2
tested with 3 V / m
Fast transient burst
to IEC 801-4 Severity rating 2
tested with 1.2 kV on supply lines
1 kV on signal lines