5
Product Information on the Manual
A5E00201782-03
Module
Peculiarities when reparameterizingBehavior of the
inputs/outputs
S7-300, ET 200, I/O modules with intrinsically-safe signals
6ES7 321-7RD00-0AB0
SM 321; DI 4 NAMUR
Supply the last valid
process value before
parameterization
SF LED shines:
If there was a pending diagnosis before
reparameterization, the SF LEDs (on the
CPU, IM, or module) may still be shining
although there is no longer a pending
diagnosis and the module is working
correctly.
Remedy:
Only reparameterize when there is no
pending diagnosis on the module, or
Remove the module, and then plug it in
again
6ES7 322 5RD00-0AB0
SM 322; DO 4 15V/20mA
Output the last valid
output value before
parameterization
6ES7 322-5SD00-0AB0
SM 322; DO 4 24V/10mA
parame
t
er
i
za
ti
on
---
6ES7 331-7RD00-0AB0
SM 331; AI 4 0/4...20mA
---
6ES7 331-7SF00-0AB0
SM 331; AI 8 TC/4 RTD
Supply the last valid
process value before
pa
r
a
m
ete
riz
at
i
o
n
---
6ES7 331-7TB00-0AB0
SM 331; AI 2 0/4...20mA
HART
parameterization
---
6ES7 332-5RD00-0AB0
SM 332; AO 4 0/4...20mA
Output the last valid
output value before
parameterization
SF LED shines:
If there was a pending diagnosis before
reparameterization, the SF LEDs (on the
CPU, IM, or module) may still be shining
although there is no longer a pending
diagnosis and the module is working
correctly.
Remedy:
Only reparameterize when there is no
pending diagnosis on the module, or
Remove the module, and then plug it in
again
6ES7 332-5TB00-0AB0
SM 332; AO 2 0/4...20mA
HART
---