2.3 Faults / diagnostics
EIP-200S Ethernet/IP Adapter Distributed I/O System
System Manual, 06/2018, A5E44345053-AB
21
2.3
Faults / diagnostics
Configuration faults
Faults in the electronic module configuration/parameterization data are handled slightly
differently depending on when they are detected. In any case, the following occurs:
Adapter Object AdapterStatus attribute indicates the appropriate code.
Identity Object Status attribute indicates a minor recoverable fault.
Fault detected at power-up or as a result of a hot swap when no I/O connections are open:
Attempts to open I/O connections result in a Device State Conflict error.
Fault detected as a result of a hot-swap when one or more I/O connections are open:
If the IO_StatusEnable attribute is TRUE, a fault is indicated in the I/O Status byte at the
beginning of the input data packet.
Output data from scanner is ignored.
Any attempt to allocate I/O connections will be rejected by the device.
Configuration fault recovery is achieved by:
Installing/removing I/O module(s) to make the actual configuration match the user-defined
configuration; and/or
Changing the configuration data to match the actual configuration.
The I/O configuration is reapplied immediately after a configuration download from the
ZNX-EIP-200S Configuration Tool, and at module startup.
Electronic module faults
When an I/O connection is active, faults in electronic modules are reported as follows:
If the IO_StatusEnable attribute is TRUE, a fault is indicated in the I/O Status byte at the
beginning of the input data packet.
The appropriate Slot Object instance SlotStatus attribute and Channel<n>Status
attribute(s) indicate the nature of the fault.
The I/O status LED state is flashing red when I/O is active.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7 EIP-200S and is the answer not in the manual?

Siemens SIMATIC S7 EIP-200S Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC S7 EIP-200S
CategoryI/O Systems
LanguageEnglish

Related product manuals