Installation and wiring
3.9 Wiring the ET 200S
EIP-200S Ethernet/IP Adapter Distributed I/O System
66 System Manual, 06/2018, A5E44345053-AB
Wiring a terminal module with a screw-type terminal
To wire a terminal module with a screw-type terminal, follow these steps:
1. Strip 11 mm (0.43 in) of insulation from the wires.
2. Insert the individual wires in the terminal.
3. Screw the ends of the individual wires onto the terminal module (torque: 0.4...0.7 Nm).
3.9.3
Wiring a terminal module with spring terminals
Features
In terminal modules with spring terminals, the individual wires are held securely when you
simply insert them in the terminal.
Prerequisites
Adhere to the wiring rules.