EasyManuals Logo

Siemens SIMATIC S7 EIP-200S User Manual

Siemens SIMATIC S7 EIP-200S
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #66 background imageLoading...
Page #66 background image
Installation and wiring
3.9 Wiring the ET 200S
EIP-200S Ethernet/IP Adapter Distributed I/O System
66 System Manual, 06/2018, A5E44345053-AB
Wiring a terminal module with a screw-type terminal
To wire a terminal module with a screw-type terminal, follow these steps:
1. Strip 11 mm (0.43 in) of insulation from the wires.
2. Insert the individual wires in the terminal.
3. Screw the ends of the individual wires onto the terminal module (torque: 0.4...0.7 Nm).
3.9.3
Wiring a terminal module with spring terminals
Features
In terminal modules with spring terminals, the individual wires are held securely when you
simply insert them in the terminal.
Prerequisites
Adhere to the wiring rules.
Tool required
3 mm screwdriver

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7 EIP-200S and is the answer not in the manual?

Siemens SIMATIC S7 EIP-200S Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC S7 EIP-200S
CategoryI/O Systems
LanguageEnglish

Related product manuals