Technical data
15.2 Technical specifications of the SIMOCODE pro C / pro S / pro V PB / pro V MR basic units
SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
333
Technical specifications of the SIMOCODE pro C / pro S / pro V PB / pro V MR basic units
Connection technology
1)
9-way sub D socket (12 Mbit)
Pin assignment acc. to DIN EN 61158-2
Terminals (1.5 Mbit)
Connection of a PROFIBUS DP cable via terminal connection or a 9-pole
sub D socket.
Pin assignment:
1: n. c.: Reserved
2: n. c.: Reserved
3: BUS B: Data line B
4: RTS: Transmission request
5: P-: Ground
6: P+: Supply voltage
7: n. c.: Reserved
8: BUS A: Data line A
9: n. c.: Reserved
-: SHIELD: Shield over connector housing
Load rating 5 V DC on PROFIBUS DP: Max. 100 mA
Support for the transfer rates defined by the PROFIBUS DP standard:
9.6 Kbit / s, 19.2 Kbit / s, 45.45 Kbit / s, 93.75 Kbit / s, 187.5 Kbit / s,
500 Kbit / s, 1500 Kbit / s, 3000 Kbit / s, 6000 Kbit / s, 12000 Kbit / s.
Note
The 5 V power supply is only sufficient to power the bus termination
module, not any other loads.
Supported data transfer rates for Modbus RTU:
300 baud, 600 baud, 1,200 baud, 2,400 baud, 4,800 baud, 9,600 baud,
19,200 baud (default), 57,600 baud
Rated control supply voltage U
s
(according to DIN EN 61131-2)
110 V to 240 V AC/DC, 50/60 Hz 24 V DC
Operating range
0.85 x Us to 1.1 x Us