Technical data
15.7 Technical data of the multifunction module
SIMOCODE pro
358 System Manual, 05/2019, A5E40507475002A/RS-AD/004
Technical data of the multifunction module
DC-13 2 A / 24 V DC;
0.55 A / 60 V DC;
0.25 A / 125 V DC
Ground-fault module function
Connectable 3UL23 residual
current transformer - feed-
through diameter
35 mm to 210 mm
Type of current to be monitored
AC and pulsating DC (type A)
Measurable line frequency
16 Hz to 400 Hz
Response value current
(settable)
0.03 A to 40 A
Measuring accuracy (relative)
ground-fault module
±5 %
Measuring accuracy (relative)
transformer 3UL23
±2.5 %
Reaction time (maximal)
100 ms
Temperature module function
Sensor circuit
Versions of the cable shielding
for the sensor circuit
Up to 30 m, cable shielding recommended
From 30 m, cable shielding necessary
Versions of the cable shielding
for the sensor circuit
Conversion time
500 ms
Type of connection
2-wire or 3-wire connection
Typical sensor circuit
PT100
PT1000 / KTY83 / KTY84 /
NTC
1 mA (typical)
0.2 mA (typical)
Measuring range open circuit
detection / short-circuit
detection
PT100 / PT1000
-50 °C ... +500 °C (open circuit, short circuit)
KTY83-110
-50 °C to +175 °C (open circuit, short circuit)
KTY84
-40 °C to +300 °C (open circuit, short circuit)
NTC
+80 °C to +160 °C (short circuit)
Measuring accuracy at an
ambient temperature of
20 °C (T20)
< ±2 K, ±1 digit
Deviation due to ambient
temperature
(as % of measured value)
0.05 per K deviation from T20
Isolation of the inputs from the
device electronics
No