Advanced commissioning
7.7 Application-specific functions
Setting the technology controller
p2200
BI: Technology controller enable (factory setting: 0)
Technology controller is enabled.
r2294
CO: Technology controller output signal
To interconnect the main speed setpoint with the technology controller output, set
p2253
CI: Technology controller setpoint 1
(factory setting: 0)
Setpoint for the technology controller.
Example:
p2253 = 2224: The inverter interconnects the fixed setpoint p2201 with the setpoint
of the technology controller.
p2220 = 1: The fixed setpoint p2201 is selected.
p2264
CI: Technology controller actual value
(factory setting: 0)
Technology controller actual value.
Technology controller ramp-up time and ramp-down time (factory setting: 1 s)
p2274
Technology controller differentiation time constant T
d
(factory setting: 0.0 s)
The differentiation improves the rise time for very slow controlled variables, e.g. a
Technology controller proportional gain K
P
(factory setting: 1,0)
Technology controller integration time (integral time) T
d
Converter with control units CU240D-2