Advanced commissioning
7.7 Application-specific functions
Advanced settings
Parameter
Remark
Limiting the output of the technology controller
In the factory setting, the output of the technology controller is limited to ± maximum speed. You must
change this limit, depending on your particular application.
Example: The output of the technology controller supplies the speed setpoint for a pump. The pump
should only run in the positive direction.
p2297
CI: Technology controller maximum limiting signal source (factory setting: 1084)
p2298
CI: Technology controller minimum limiting signal source (factory setting: 2292)
p2291
CO: Technology maximum limiting (factory setting: 100 %)
p2292
CO: Technology minimum limiting (factory setting: 0 %)
Manipulating the actual value of the technology controller
p2267
Technology controller upper limit actual value (factory setting: 100 %)
p2268
Technology controller lower limit actual value (factory setting: -100 %)
p2269
Technology controller gain actual value (factory setting: 100 %)
p2271
Technology controller actual value inversion (sensor type)
0:
No inversion
1: Inversion actual value signal
If the actual value decreases with increasing motor speed, then p2271 must
be set = 1.
p2270
Technology controller actual value function
0:
No function
1:
2:
x
2
3: x
3
For further information refer to the function block diagrams 7950 ff of the List Manual.
Converter with control units CU240D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB
191