Adapt fieldbus configuration
6.2 PROFIdrive profile for PROFIBUS and PROFINET
Signal inter-
connection
in the in-
verter
1 = No quick stop (OFF3) The motor can be switched on (ON com-
3 0 = Inhibit operation Immediately switch-off motor (cancel pulses). p0852[0] =
r2090.3
Switch-on motor (pulses can be enabled).
4 0 = Disable RFG The inverter immediately sets its ramp-
function generator output to 0.
p1140[0] =
r2090.4
The ramp-function generator can be enabled.
5 0 = Stop RFG The output of the ramp-function generator
stops at the actual value.
p1141[0] =
r2090.5
1 = Enable RFG The output of the ramp-function generator
6 0 = Inhibit setpoint The inverter brakes the motor with the ramp-
down time p1121 of the ramp-function genera-
p1142[0] =
r2090.6
1 = Enable setpoint Motor accelerates with the ramp-up time
7 0 → 1 = Acknowledge faults Acknowledge fault. If the ON command is still
active, the inverter switches to"closing lockout"
state.
p2103[0] =
r2090.7
10 0 = No control via PLC Inverter ignores the process data from the
p0854[0] =
r2090.10
1 = Control via PLC Control via fieldbus, inverter accepts the pro-
cess data from the fieldbus.
11 1 = Direction reversal Invert setpoint in the inverter. p1113[0] =
13 ---
1)
1 = MOP up Increase the setpoint saved in the motorized
p1035[0] =
14 ---
1)
1 = MOP down Reduce the setpoint saved in the motorized
p1036[0] =
15 CDS bit 0 Reserved Changes over between settings for different
operation interfaces (command data sets).
p0810 =
If you change over from another telegram to telegram 20, then the assignment of the previous
Converter with control units CU240D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB