Adapt fieldbus configuration
6.2 PROFIdrive profile for PROFIBUS and PROFINET
Signal inter-
connection
in the in-
verter
0 1 = Ready to start Power supply switched on; electronics initial-
p2080[0] =
1 1 = Ready Motor is switched on (ON/OFF1 = 1), no fault
is active. With the command "Enable opera-
tion" (STW1.3), the inverter switches on the
p2080[1] =
r0899.1
2 1 = Operation enabled
Motor follows setpoint. See control word 1, bit
3.
p2080[2] =
3 1 = Fault active The inverter has a fault. Acknowledge fault
p2080[3] =
4 1 = OFF2 inactive Coast down to standstill is not active. p2080[4] =
5 1 = OFF3 inactive Quick stop is not active. p2080[5] =
6 1 = Closing lockout active It is only possible to switch on the motor after
p2080[6] =
7 1 = Alarm active Motor remains switched on; no acknowl-
p2080[7] =
8 1 = Speed deviation within the
Setpoint / actual value deviation within the
p2080[8] =
9 1 = Master control requested The automation system is requested to ac-
cept the inverter control.
p2080[9] =
10
1 = Comparison speed reached or
exceeded
Speed is greater than or equal to the corre-
p2080[10] =
11 1 = current or
torque limit
1 = torque limit
reached
Comparison value for current or torque has
been reached or exceeded.
p2080[11] =
r0056.13 /
12 ---
1)
1 = Holding
Signal to open and close a motor holding
p2080[12] =
13 0 = Alarm, motor overtemperature -- p2080[13] =
14
1 = Motor rotates clockwise
Internal inverter actual value > 0
p2080[14] =
r2197.3
0 = Motor rotates counterclock-
Internal inverter actual value < 0
15 1 = CDS display 0 = Alarm, in-
verter thermal
p2080[15] =
r0836.0 /
If you change over from another telegram to telegram 20, then the assignment of the previous
Converter with control units CU240D-2
96 Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB