8.4 Controlling the external connections of the inverter
Installation and Operating Instructions SINAMICS G180
Operating Instructions, 02/2019, 4BS0751-007
147
Potential for output (PTC) (-X3) max. 690 V
Potential for digital outputs (-X2:37-42) max. 250 V
Potential for digital outputs (-X2:30,31) max. 250 V
Potential for digital outputs (-X2:32,33) max. 250 V
Potential for digital outputs (-X2:34-36) max. 250 V
Potential for digital outputs (-X2:43-45) max. 250 V
Potential for digital outputs (-X2:46-47) max. 250 V
Potential for digital outputs (-X2:48-49) max. 250 V
Potential for digital inputs (-X2:1-26)
Potential for ETV (ETV = input isolating amplifier, analog inputs -X2:27-29,50-58,
DVC A
Potential for ATV (output isolating amplifier, analog outputs -X2:60-67,70-71)
Potential for control electronics/CB08 (inverter electronics, ext. display -X26,
sin/cos-tacho -X25, USB-A -X50A, USB-B -X50B)
DVC A
Potential for RS485 (ext. display/RS232 -X51)
Potential SELV, safety extra-low voltage in accordance with EN 60950-1 (BUS
DVC A
Figure 8-15 Insulation concept
DVC (Decisive Voltage Class) is the classification of the voltage range used to determine
protective measures against electric shock hazards
Table 8- 2 Limit values of the DVC according to EN 61800-5-1
Alternating voltage
(rms value)
Alternating voltage
(peak value)
Direct voltage
(average value)
For more detailed information about control cable terminals, please refer to section
"Technical data of control cable terminals (Page 201)".