Installation   
5.5 Mounting an external display (option) 
  Installation and Operating Instructions SINAMICS G180 
88  Operating Instructions, 02/2019, 4BS0751-007 
 
Mounting an external display (option) 
The external display with the item number L0296033 has the same functionality as the 
internal display. You can connect the display to the inverter at two connectors: 
●  At RJ-10 connector -X26 for a maximum cable length of 5 m. 
●  At the 9-pin D-sub connector -X51 and with a supplementary 24 V voltage supply for a 
maximum cable length of 1000 m. 
Use the display in control panels or doors. Note the following dimensions for the opening: 
Width x Height [mm]: 138
+1
 × 92
+0.8
 
The degree of protection is IP54. 
 
Figure 5-3  Dimension drawing - External display 
Connection for installation in the switch cabinet door with maximum 5 meters connection cable length 
Use the connecting cable with item number L0330600. 
1.  Shorten the cable to the required length. 
2.  Connect up the cables using end sleeves as illustrated in the diagram below.