Electrical connection
6.7 External control voltage
Installation and Operating Instructions SINAMICS G180
112 Operating Instructions, 02/2019, 4BS0751-007
6.7.3
Connecting the external 24 V DC control voltage
6.7.3.1
Protecting/fusing the external 24 V DC control voltage
NOTICE
External control voltage without fuse protection
If you use an external control voltage without suitable protection (e.g. fuses), then
overloads and short-circuits can occur. Material damage can result.
The device may only be operated with a protected external control voltage. Note the
following recommendation.
Install one of the following options to protect the external control voltage:
Miniature fuse in accordance with EN 60127: 6 A, slow acting, maximum 100 VA
Miniature circuit-breaker: 6 A, characteristic D, maximum 100 VA
6.7.3.2
Switching over the hardware to an external 24 V DC control voltage
Change the converter from internal control voltage via the DC link to external control
voltage.
Replace the PC board switch mode power supply L0353151 by PC board SNT24V
L0353161.
Procedure
Connect the external control voltage to the terminals 1 (0 V) and 2 (+24 V).