Operation
8.8 Examples / Applications
Installation and Operating Instructions SINAMICS G180
174 Operating Instructions, 02/2019, 4BS0751-007
● Terminal -X3:92/:93:
This input is used as prewarning for the motor temperature monitoring. If you wish to use
this function, then you must remove the existing resistor, and connect the appropriate
prewarning motor PTC thermistor.
Peripheral board 2 or 4 is required for monitoring
The monitoring function is only available if the required peripheral board 2 or peripheral
board 4 is inserted in the SINAMICS G180
If the peripheral board 1 or peripheral board 3 is installed, then although the terminals
are available, there is no evaluation. There is no monitoring.
More detailed information can be found in Chapter "Peripheral boards 1 to 4" (Page 37).