EasyManua.ls Logo

Siemens SINAMICS V90 - Main circuit wiring

Siemens SINAMICS V90
158 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Task navigation
SINAMICS V-ASSISTANT Online Help
116 Operating Manual, 04/2017, A5E36618042-003
5.
Perform the servo on for the drive with host controller and tuning starts.
For example, you can use the following method to run the motor.
Implement servo
on for the drive with Jog.
Enter the speed for the motor and press the direction button to
let the motor run.
6.
To achieve the desired system performance, you can change the dyn
amic factors or
related configuration parameters during tuning.
7.
If the drive performance is acceptable, disable the tuning function by servo off and set
p29021 = 0.
8.
Copy the tuned parameters from RAM to ROM to save them.
Resonance suppression with real-time auto tuning (p29021=3, p29024.6=1)
The resonance suppression function is used together with the real-time auto tuning function.
The function is activated by default.
When you use real-time auto tuning function, you are recommended to disable the
resonance suppression function to get a high dynamic performance if there is no resonance
in the machine.
The function can be activated/deactivated with the bit 6 of p29024.
When you choose to use the resonance suppression function with real-time auto tuning, the
servo drive performs real-time detection of the resonance frequency and configures the
following notch filter relevant parameters accordingly:
Parame-
ter
Value range
Default
value
Unit
Description
p1663
0.5 to 16000
1000
Hz
Natural frequency of current notch filter 2 denominator.
p1664
0.001 to 10
0.3
-
Damp of current notch filter 2 denominator.
p1665
0.5 to 16000
1000
Hz
Natural frequency of current notch filter 2 numerator.
p1666
0.0 to 10
0.01
-
Damp of current notch filter 2 numerator.

Table of Contents

Other manuals for Siemens SINAMICS V90

Related product manuals