SINAMICS V-ASSISTANT Online Help
Operating Manual, 04/2017, A5E36618042-003
95
Wiring
The digital inputs support both PNP and NPN types of wirings. You can find detailed
information from the following diagrams:
NPN wiring
PNP wiring
DOs
You can assign a maximum of ten internal digital output signals to the SINAMICS V90 PN
servo drive. For detailed information about these signals, see the table below:
Name
Descriptions
Control mode
S
EPOS
RDY Servo ready
1: ready to operate
0: drive not ready (alarm occurs or enable signal is miss-
ing)
FAULT Fault
1: in fault status
0: no fault
ZSP Zero speed detection
1: motor speed is equal with or lower than the zero
speed (can be set with parameter p2161).
0: motor speed is higher than zero speed + hysteresis
(10 rpm).
TLR Torque limit reached
1: the generated torque has nearly (internal hysteresis)
reached the value of the positive torque limit, negative
torque limit or analog torque limit
0: the generated torque has not reached the limit