Terminal Designation
1)
Technical data
Switching frequency
for ohmic load: Max. 100 Hz
For inductive load: Max. 0.5 Hz
For lamp load: max. 10 Hz
Lamp load: max. 5 W
Type: Spring-loaded terminal 3
1)
DI: digital input; DI/DO: bidirectional digital input/output; M: electronics ground; M2: reference potential
2)
The rapid inputs can be used as probe inputs or as inputs for the external zero mark
3)
Data for: V
cc
= 24 V; load 48 Ω; high ("1") = 90% V
out
; low ("0") = 10% V
out
The maximum cable length that can be connected is 30 m.
Note
Ensuring the function of digital inputs
An open input is interpreted as "low".
To enable the digital inputs (DI) to function, terminal M2 must be connected.
This is achieved by using one of the following measures:
1. Providing the ground reference of the digital inputs
2. A jumper to terminal M
Note: This removes isolation for these digital inputs.
Note
If the 24 V supply is briefly interrupted, then the digital outputs are deactivated during this time.
3.1.2.5 X124 electronics power supply
Table 3-5 X124 electronics power supply
Terminal Designation Technical data
+ Electronics power supply Voltage: 24 V DC (20.4 ... 28.8 V)
Current consumption: max. 6.5 A
(including DRIVE-CLiQ and digital outputs)
Max. current via jumper in connector: 20 A (15 A ac‐
cording to UL/CSA)
+ Electronics power supply
M Electronics ground
M Electronics ground
Type: Screw terminal 2
Control Units
3.1 Control Unit CU320-2 PN (PROFINET)
Supplementary component descriptions
18 Manual, 06/2019