4.1.2.2 X451 CAN bus interface
Table 4-1 X451: CAN bus interface
Pin Designation Technical data
1 Reserved, do not use -
2 CAN_L CAN signal (dominant low)
3 CAN_GND CAN ground
4 Reserved, do not use -
5 CAN_SHLD Optional shield
6 GND CAN ground
7 CAN_H CAN signal
8 Reserved, do not use -
9 Reserved, do not use -
Type: 9-pin SUB D socket
NOTICE
Destruction of the CAN bus interface as a result of an incorrect connector
If PROFIBUS connectors are connected to CAN bus interfaces during operation, this may lead
to the CAN bus interfaces being destroyed.
Do not connect PROFIBUS connectors to CAN bus interfaces.
4.1.2.3 X452 CAN bus interface
Table 4-2 X452: CAN bus interface
Pin Designation Technical data
1
9
1 Reserved, do not use -
2 CAN_L CAN signal (dominant low)
3 CAN_GND CAN ground
4 Reserved, do not use -
5 CAN_SHLD Optional shield
6 GND CAN ground
7 CAN_H CAN signal
8 Reserved, do not use -
9 Reserved, do not use -
Type: 9-pin SUB-D male