LED Color Status Description, cause Remedy
COM
PROFIdrive
cyclic opera‐
tion
Off Cyclic communication has not (yet) taken place.
Comment:
PROFIdrive is ready for communication if the Con‐
trol Unit is ready (see LED RDY).
Green Continuous
light
Cyclic communication is taking place.
Flashing
light
0.5 Hz
Full cyclic communication has not yet taken place.
Possible causes:
The controller is not transferring any setpoints.
During isochronous operation, no global control
(GC) or a faulty global control (GC) is
transferred by the controller.
Red Flashing
light
0.5 Hz
PROFIBUS master is sending wrong parameteri‐
zation/configuration data
Adapt configuration between
master/controller and CU
Flashing
light
2 Hz
Cyclic bus communication has been interrupted or
could not be established
Remove fault
OPT
(OPTION)
Off Electronics power supply is missing or outside the
permissible tolerance range.
Component is not ready.
Option board not installed or no associated drive
object has been created.
Check power supply and/or
component
Green Continuous
light
Option board is ready.
Flashing
light
0.5 Hz
Depends on the Option Board used
2)
.
Red
Continuous
light
Depends on the Option Board used
2)
.
Flashing
light
0.5 Hz
Depends on the Option Board used
2)
.
Flashing
light
2 Hz
At least one fault is present in this component. Op‐
tion board not ready (e.g. after switching on).
Remove the fault and acknowl‐
edge
RDY and
COM
Red Flashing
light
2 Hz
Bus error - communication has been interrupted Remove fault
RDY and
OPT
Orange Flashing
light
0.5 Hz
The firmware of the connected option board is be‐
ing updated.
1)
DCP = Discovery and Configuration Protocol
DCP is used by PROFINET to determine PROFINET devices and allow basic settings. Therefore this function is only
available on the CU320-2 DP if the CBE20 Option Board is inserted.
Further information can be found in the SINAMICS S120 Function Manual "Communication".