ANAI-CE-2EL
Channel 2 (CH2) of the measuring-transducer module can be used to monitor a direct voltage of 0 VDC to
+300 VDC. Channel 1 (CH1) of the plug-in module has no function and cannot be used. For the connection to
the measuring-transducer modules, the following conditions apply:
•
Channel 2 (CH2) is an input with HLV (Hazardous Live Voltage)
•
For CH2, use a core cross section of 1.0 mm² to 2.5 mm² (AWG 18-14).
•
Leave the terminal inserted even if the plug-in module is not being used in the device.
!
DANGER
Dangerous voltage when working on the plug-in module.
Disregarding the measures may lead to death or severe injuries.
²
When working on (installation/removal) the modules or terminals, make sure that no voltage is
applied.
Product Code P1Z3704
Figure
Terminal Diagram
Connector type 8-pin terminal spring
Input channels 1 direct voltage input, Channel 2 (CH2)
Measuring range 0 VDC to +300 VDC
Tolerance 0.2% of measuring range or 500 mV
Input impedance 260 kΩ
Max. permissible voltage against
ground on the measuring inputs
DC 300 V
4.3.3
Plug-In Modules
4.3 Measuring-Transducer Modules
SIPROTEC 5, Hardware Description, Manual 181