Installing Current and Voltage Terminals
Description
[dwklepos-030211-01.tif, 1, --_--]
Figure 5-22 Current and Voltage Terminals with Spring Clips
(1) Current-terminal block
(2) Voltage-terminal block
(3) Spring clips
The spring clips fix the terminal block in place.
[sc_klepos-020414-01, 1, --_--]
Figure 5-23 Voltage Terminal with Screw Connection
Current-Terminal Block of the Modular Devices
The following transformers can optionally be installed in a current-terminal block for modular devices:
4 protection-class current transformers
3 protection-class current transformers and 1 instrument transformer
4 instrument transformers
Protection-class current transformers on modular devices are transformers with a rated current of 1 A or 5 A
and a device-dependent measuring range of 20 x rated current or 100 x rated current.
i
i
NOTE
You can read the type of the current transformer used on the side of the terminal block:
C73334A 1A18 *7* = 4 protection-class current transformers
C73334A 1A18 *8* = 3 protection-class current transformers and 1 instrument transformer
C73334A 1A18 *9* = 4 instrument transformers
5.7
5.7.1
Working on the Device
5.7 Installing Current and Voltage Terminals
SIPROTEC 5, Hardware Description, Manual 183
C53000-G5040-C002-C, Edition 10.2017

Table of Contents

Other manuals for Siemens SIPROTEC 5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 5 and is the answer not in the manual?

Siemens SIPROTEC 5 Specifications

General IconGeneral
SeriesSIPROTEC 5
Communication ProtocolsIEC 61850, DNP3, Modbus
CybersecurityRole-based access control, secure communication
Modular DesignYes
Hardware RedundancyOptional
Operating Temperature-25°C to +70°C
Digital InputsConfigurable, number depends on I/O modules
Digital OutputsConfigurable, number depends on I/O modules
Analog InputsConfigurable, number depends on I/O modules
Current Transformer InputsConfigurable, number depends on I/O modules
Voltage Transformer InputsConfigurable, number depends on I/O modules
Time SynchronizationIRIG-B, SNTP, PTP
Protection FunctionsOvercurrent, Differential, Distance, Over/Under Voltage, Frequency
Housing19-inch Rack Mount
DimensionsDepends on module configuration
WeightDepends on module configuration
Voltage Input24V DC, 48V DC, 110V DC, 125V DC, 220V DC, 250V DC