Operating Conditions
The protection device is designed for flush mounting in conventional relay rooms and systems such that elec-
tromagnetic compatibility (EMC) is ensured with proper flush mounting.
Siemens additionally recommends:
Use contactors and relays that work within the same cabinet or the same relay panel with digital protec-
tion equipment, only with suitable quenching equipment.
With switchgear rated at 100 kV or higher, provide external connecting lines with shielding grounded at
both ends that is capable of carrying current. No special measures are necessary in medium-voltage
systems.
Removing or plugging in individual modules under live voltage is prohibited. Some components are elec-
trostatically sensitive in the removed state. Pay attention to the ESD specifications (Electrostatically Sensi-
tive Devices). There is no danger for the components when they are installed.
6.10
Technical Data
6.10 Operating Conditions
208 SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-C, Edition 10.2017

Table of Contents

Other manuals for Siemens SIPROTEC 5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 5 and is the answer not in the manual?

Siemens SIPROTEC 5 Specifications

General IconGeneral
SeriesSIPROTEC 5
Communication ProtocolsIEC 61850, DNP3, Modbus
CybersecurityRole-based access control, secure communication
Modular DesignYes
Hardware RedundancyOptional
Operating Temperature-25°C to +70°C
Digital InputsConfigurable, number depends on I/O modules
Digital OutputsConfigurable, number depends on I/O modules
Analog InputsConfigurable, number depends on I/O modules
Current Transformer InputsConfigurable, number depends on I/O modules
Voltage Transformer InputsConfigurable, number depends on I/O modules
Time SynchronizationIRIG-B, SNTP, PTP
Protection FunctionsOvercurrent, Differential, Distance, Over/Under Voltage, Frequency
Housing19-inch Rack Mount
DimensionsDepends on module configuration
WeightDepends on module configuration
Voltage Input24V DC, 48V DC, 110V DC, 125V DC, 220V DC, 250V DC