Type of
Construction
Max. Total wWidth x Max. Total Height x Max. Total Depth
33
, Rounded to full mm
Surface-
mounted device
with detached
on-site operation
panel with
IO240
150 mm x
315 mm x
277 mm
225 mm x
315 mm x
277 mm
300 mm x
315 mm x
277 mm
375 mm x
315 mm x
277 mm
450 mm x
315 mm x
277 mm
Surface-
mounted device
with detached
on-site operation
panel with
IO111
150 mm x
315 mm x
243 mm
225 mm x
315 mm x
243 mm
300 mm x
315 mm x
243 mm
375 mm x
315 mm x
243 mm
450 mm x
315 mm x
243 mm
Plug-In Module Dimensions
Type of Construction Max. Width x Max. Height x Max. Depth
USART-Ax-xEL, ETH-Bx-xEL 61 mm x 45 mm x 121 mm
USART-Ax-xFO, ETH-Bx-xFO (without protective cover) 61 mm x 45 mm x 133 mm
ANAI-CA-4EL, ANAI-CE-2EL 61 mm x 45 mm x 120 mm
ARC-CD-3FO 61 mm x 45 mm x 121 mm
Minimum Bending Radii of the Connecting Cables Between the On-Site Operation Panel and the Base Module
Fiber-optic cable
R = 50 mm
Pay attention to the length of the cable protection
sleeve, which you must also include in calculations.
D-Sub cable R = 50 mm (minimum bending radius)
Degree of Protection According to IEC 60529
For equipment in the surface-mounting housing
IP54
35
for front
For equipment in the flush-mounting housing
IP54
35
for front
For operator protection (back side) IP2x for current terminal (installed)
IP2x for voltage terminal (installed)
Degree of pollution, IEC 60255-27 2
Maximum operating altitude above sea level 2000 m (6561.68 ft)
UL Note
Type 1 if mounted into a door or front cover of an enclosure.
When expanding the device with the 2nd device row, then they must be mounted completely inside an
enclosure.
33
Including current terminal, excluding USB port cover
35
The supplied plug-in strips must be used for expansion modules with LEDs.
Technical Data
6.13 Design Data
252 SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-N, Edition 04.2022