Functions
2.11 Ground Fault Protection 64, 67N(s), 50N(s), 51N(s)
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A4, Release date 08.2010
179
Determination of Direction
When determining the sensitive ground fault direction it is not the current value that is crucial, but the part of 
the current which is perpendicular to a settable directional characteristic (axis of symmetry). As a prerequisite 
for determining the direction, the displacement voltage V
0
 must be exceeded as well as a configurable current 
part influencing the direction (active or reactive component).
The following figure illustrates an example using a complex vector diagram in which the displacement voltage 
V
0
 is the reference magnitude of the real axis. The active part 3I0
real
 of current 3I
0
 is calculated with reference 
to the displacement voltage V
0
 and compared with setting value RELEASE DIRECT.. The example is therefore 
suitable for ground fault direction in resonant grounded systems where quantity 3I
0
 · cos ϕ is relevant. The di-
rectional limit lines are perpendicular to axis 3I0
real
.
Figure 2-58 Directional characteristic for cos–ϕ–measurement
The directional limit lines may be rotated by a correction angle (address PHI CORRECTION) up to ± 45°. There-
fore, in grounded systems it is possible e.g. to increase sensitivity in the resistive-inductive range with a rotation 
of –45°, or in case of electric machines connected to the busbar of an ungrounded power system in the resis-
tive-capacitive range with a rotation of +45° (see the following Figure). Furthermore the directional limit lines 
may be rotated by 90° to determine ground faults and their direction in isolated systems.