Functions
7.8 Asymmetry
SIRIUS 3RW55 soft starter
128 Manual, 08/2018, A5E35630887002A/RS-AB/002
Parameters
Parameters
Description
Pump cleaning - mode
Deactivated
(factory setting)
The pump cleaning function is deactivated.
Manual
The pump cleaning function is started with the aid of a control
command by means of an input action at the digital input or in the
process image outputs.
Pump cleaning - time During the cleaning time, the pump runs at reduced speed and
the maximum possible torque.
Factory setting: 20 s
Setting range: 1 ... 30 s
Increment: 1 s
Pump cleaning - cycles During a cycle, the pump rotation changes direction several
times.
Factory setting: 3
Setting range: 1 ... 10
Increment: 1
Pump cleaning - start/stop
parameters
You can select the parameters for starting and stopping the pump
for different cleaning processes here. For example, you can make
different settings for starting and stopping in parameter set 2 than
for the normal starting and stopping procedure.
Parameter set 1
The pump cleaning function is carried out with the starting and
ramp-down parameters of parameter set 1.
Parameter set 2
The pump cleaning function is carried out with the starting and
ramp-down parameters of parameter set 2.
Parameter set 3
The pump cleaning function is carried out with the starting and
ramp-down parameters of parameter set 3.
Operating parameters
(factory setting)
The pump cleaning function is carried out with the starting and
ramp-down parameters of the currently selected parameter set.