ID/
Icons
Diagnostic Action Comment
109 Medium temperature Value above warning limit. Check process con‐
ditions or align limit to normal operation. Adjust
parameter 'Upper warning limit'
110 Medium temperature Value below warning limit. Check process con‐
ditions or align limit to normal operation. Adjust
parameter 'Lower warning limit'
111 Medium temperature Value below alarm limit. Check process condi‐
tions or align limit to normal operation. Adjust
parameter 'Lower alarm limit'
132 Standard volume flow Value above alarm limit. Check process condi‐
tions or align limit to normal operation. Adjust
parameter 'Upper alarm limit'
Only hydrocarbon
133 Standard volume flow Value above warning limit. Check process con‐
ditions or align limit to normal operation. Adjust
parameter 'Upper warning limit'
Only hydrocarbon
134 Standard volume flow Value below warning limit. Check process con‐
ditions or align limit to normal operation. Adjust
parameter 'Lower warning limit'
Only hydrocarbon
135 Standard volume flow Value below alarm limit. Check process condi‐
tions or align limit to normal operation. Adjust
parameter 'Lower alarm limit'
Only hydrocarbon
136 Totalizer 1 Value above alarm limit. Check process condi‐
tions or align limit to normal operation. Adjust
parameter 'Upper alarm limit'
137 Totalizer 1 Value above warning limit. Check process con‐
ditions or align limit to normal operation. Adjust
parameter 'Upper warning limit'
Diagnostics and troubleshooting
9.8 Fault codes and corrective actions
SITRANS FST030 (Modbus)
Operating Instructions, 08/2018, A5E37367739-AD 107