3.2.1.1 Installation location requirements
NOTICE
Aggressive atmospheres
Damage to device through penetration of aggressive vapors.
Ensure that the device is suitable for the application.
NOTICE
Direct sunlight
Damage to device.
The device can overheat or materials become brittle due to UV exposure.
Protect the device from direct sunlight.
Make sure that the maximum permissible ambient temperature is not exceeded. Refer to
the information in Technical speci󹪝cations SITRANS MS200 (Page65).
3.2.2 General description
NOTICE
Wrong assembly
Wrong assembly can damage the asset or the SITRANS MS200.
Carefully read the safety instructions before mounting.
SITRANS MS200 has an M8 female thread for the installation, see Dimension drawings
SITRANSMS200.
For thread M8:
minimum screw-in depth 5,5mm
maximum screw-in depth 13mm
screw-in torque min. 18Nm and max. 20Nm
screw-in material stainless steel
Use an anaerobic adhesive thread locker.
SITRANS MS200 can be mounted in various ways utilizing its threaded M8 hole. As examples
for mounting you can:
directly mount SITRANS MS200 to an existing stud bolt
use a short threaded bolt to mount SITRANS MS200 to a threaded hole
use a clamp shell to mount SITRANS MS200 to a pipe
Installing/mounting
3.2Installation instructions SITRANS MS200
SITRANS CC220 and SITRANS MS200
36 Compact Operating Instructions, 10/2023 - DRAFT, A5E...-AA