4. Connect new SITRANS CC220.
5. Reconnect old SITRANS MS200 with SITRANS SCM IQto the same MindSphere asset.
6. Reset SITRANS MS200.
AUTOHOTSPOT
6.2.5 Updating rmware of SITRANS CC220
Introduction
If a rmware update is required, you receive a notication in SITRANSSCMIQ.
Procedure
1. Download the rmware update le for SITRANSCC220.
Dowload rmware update le for SITRANS CC220 (
https://
support.industry.siemens.com/cs/ww/en/ps/28832/dl)
2. Plug in an empty and fat32 formatted USB stick with 16GB free disk space into your PC.
3. Store the *.SWU le on the USB stick.
4. Insert the USB stick into SITRANSCC220 USB1-X60 port.
⇒USERLED2 is blinking green (takes 5 to 10 minutes).
⇒ Both USER LEDs are blinking orange while the rmware update is ongoing (takes 5 to 10
minutes). We recommend you to remove the USB stick from SITRANS CC220.
⇒If the rmware update passed the USERLEDs light green for 10 seconds.
⇒SITRANSCC220 reboots.
If rmware update fails
⇒USER 1 LED is blinking orange.
⇒USER 2 LED is blinking red.
To go back to old working state, press RESET button, and SITRANSCC220 will reboot.
6.3 Maintenance and repair work for SITRANS MS200
6.3.1 Basic safety notes
The device is maintenance-free. However, a periodic inspection according to pertinent directives
and regulations must be carried out.
An inspection can include, for example, check of:
• Ambient conditions
• Seal integrity of the cover
Service and maintenance
6.3Maintenance and repair work for SITRANS MS200
SITRANS CC220 and SITRANS MS200
Compact Operating Instructions, 10/2023 - DRAFT, A5E...-AA 51