4.2.2 Connecting SITRANS CC220
Before connecting SITRANSCC220
You have connected functional grounding (Page40).
You are using the supplied terminal.
A two-core cable meet the following requirements:
a copper (Cu) cable with cross-section of 0.75to 2.5mm
2
rated temperature 70°C
A slotted screwdriver with a 3mm blade.
Procedure
32:(5
2))
1. Switch o󹪜 the power supply.
2. Connect the lines to the connecting terminal with a torque of 0.56Nm (5lb-in).
3. Connect the connecting terminal to the connection for the power supply.
⇒ STAT LED is blinking green.
⇒ PWR LED is lighting green.
4. Integrate SITRANS CC220 into your network using Ethernet port X1 LAN - P1.
Figure4-1 Ethernet connection X1 LAN - P1
5. Make sure SITRANS CC220 has an internet connection.
⇒ After onboarding:
If there is an active internet connection USER2LED is lighting green.
If there is no internet connection USER2LED is blinking fast orange.
Connecting
4.2Connecting SITRANS CC220
SITRANS CC220 and SITRANS MS200
42 Compact Operating Instructions, 10/2023 - DRAFT, A5E...-AA