Building Technologies Boiler sequence controller RMK770 CE1P3132en
HVAC Products 7 Boiler control 23.04.2009
Main menu > Commissioning > Settings > … or
Main menu > Settings > Boiler … > Fault settings > Checkb signal burner
Operating line Range Factory setting
Signal delay start 00.05…59.55 m.s 04.00 m.s
Signal interruption operation 00.00…59.55 m.s 20.00 m.s
Impact of fault No stop / Stop Stop
Main menu > Commissioning > Settings > … or
Main menu > Settings > Boiler … > Fault settings > Checkb sign shutoff valve
Operating line Range Factory setting
Signal delay start 00.05…59.55 m.s 02.00 m.s
Main menu > Commissioning > Settings > … or
Main menu > Settings > Boiler … > Fault settings > Flue temp supervision
Operating line Range Factory setting
Flue gas temperature limit value ---- / 8…400 °C ---- °C
Impact of fault No stop / Stop No stop
Fault priority Urgent / Nonurgent Nonurgent
Main menu > Commissioning > Settings > … or
Main menu > Settings > Boiler … > Fault settings > Fault input 1
Operating line Range Factory setting
Fault text A…Z Water shortage
Impact of fault No stop / Stop Stop
Fault acknowledgement None / Acknowledge /
Acknowledge and reset
Acknowledge
Fault priority Urgent / Nonurgent Urgent
Fault status signal delay 00.00…59.55 m.s 00.05 m.s
Main menu > Commissioning > Settings > … or
Main menu > Settings > Boiler … > Fault settings > Fault input 2
Operating line Range Factory setting
Fault text A…Z Overpressure
Impact of fault No stop / Stop Stop
Fault acknowledgement None / Acknowledge /
Acknowledge and reset
Acknowledge
Fault priority Urgent / Nonurgent Urgent
Fault status signal delay 00.00…59.55 m.s 00.05 m.s
Main menu > Commissioning > Settings > … or
Main menu > Settings > Boiler … > Fault settings > Fault input 3
Operating line Range Factory setting
Fault text A…Z Underpressure
Impact of fault No stop / Stop Stop
Fault acknowledgement None / Acknowledge /
Acknowledge and reset
Acknowledge
Fault priority Urgent / Nonurgent Urgent
Fault status signal delay 00.00…59.55 m.s 00.05 m.s
The type of fault input can be parameterized at menu item Settings > Inputs at the rele-
vant terminal.