Building Technologies Boiler sequence controller RMK770 CE1P3132en
HVAC Products 10 Heating circuit control 23.04.2009
Priority Name Explanation
h
i / j
Presence and timer
button
The current time program can be overridden by
presence button
h or timer button i.
The timer button at digital input
j (or of a third-
party KNX device) can also override the room
operating mode.
If 2 or more functions are triggered, the function
activated last prevails.
k
Special day contact
The current 24-hour program gets overridden by
the special day contact. The special day program is
activated in the time switch
l
Holidays contact
The current 7-day program is overridden by the
holidays contact. The room operating mode can be
selected
Calendar
If a special day is active, the associated 24-hour
program of the time switch is activated. Holidays, if
entered, are overridden. If holiday mode is active,
the selected room operating mode is used
Time switch
In the time switch, the associated 24-hour program
is activated in accordance with the current week-
day. The 24-hour program forwards the current
room operating mode, the next setpoint, and the
time up to the next switching point
10.4 Room temperature setpoints
10.4.1 Settings
The setpoints for the 4 room operating modes can be preselected by the plant operator
via operation. The setting values limit one another.
Main menu > Heating circuit > Room setpoints
Main menu > Settings > Heating circuit > Room setpoints
Operating line Range Factory setting
Comfort 19…35 °C 21 °C
Precomfort 16…21 °C 19 °C
Economy 10…19 °C 16 °C
Protection 1…16 °C 10 °C
The preselected setpoints of Comfort
and Precomfort mode can be readjusted by
±3 K on the QAW740 room unit.
It is possible to use a conventional room temperature setpoint adjuster (absolute or
relative). For more detailed information, refer to the 2 subsections below.
The 4 setpoints are readjusted according to the following rules:
• Parallel readjustment of Comfort and Precomfort setpoint
• When the Economy setpoint is reached, it is shifted along with the Precomfort setpoint
• With the Protection setpoint, the Comfort, Precomfort and Economy setpoints are
limited
The effective setpoint is displayed on the service level and on the Info page.
Main menu > Heating circuit > Inputs/setpoints
Operating line Range Factory setting
Current room temp setpoint …°C
Room setpoint absolute* …°C
Room setpoint relative* …°C
* Only if configured via extra configuration
Remote setpoint
adjuster
Display of inputs/setpoints