Building Technologies Boiler Sequence Controller RMK770 CE1P3132en
HVAC Products 4 General settings 23.04.2009
4.2 Selecting the language
Every RMK770 controller has a number of languages loaded.
When switching on the controller for the first time, the required language must be entered.
But the language can also be changed later during operation.
Depending on the type of controller, the following languages with the relevant instruc-
tions are available:
Product no. Language 1 Language 2 Language 3 Language 4 Language 5 Language 6
RMK770-1 German French Italian Spanish
RMK770-2 German English French Dutch
RMK770-3 Swedish Finnish Norwegian Danish
RMK770-4 Polish Czech Slowakian Hungarian Russian Bulgarian
RMK770-5 Serbian Croatian Rumanian Slowenian Greek Turkish
Main menu > Commissioning > Settings > … or
Main menu > Settings > Device
Operating line Range Factory setting
Language English*
* Available with all types
4.3 Selecting the unit of temperature
On the RMK770, the unit of temperature can be switched between °C/ K
and °F.
Main menu > Commissioning > Settings > … or
Main menu > Settings > Device
Operating line Range Factory setting
Unit °C / °F °C
4.4 Contrast of the operator unit’s display
The contrast of the display can be matched to ambient conditions, thus improving
readability.
Main menu > Commissioning > Settings > … or
Main menu > Settings > Device
Operating line Range Factory setting
Contrast 0…100% 50%
4.5 Text entry
4.5.1 Device name and file name
Main menu > Commissioning > Settings > … or
Main menu > Settings > Texts
Operating line Range Factory setting
Device name
Max. 20 characters
The text of the device name appears on the start page in place of “Welcome“.
The file name is only of importance in connection with the ACS7… plant operating
software; the text can be edited here.
Setting
Setting
Setting
Setting
Device name
File name