EasyManua.ls Logo

Siemens Synco 700 Series - Heat Request Modulating

Siemens Synco 700 Series
232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
141/232
Building Technologies Boiler sequence controller RMK770 CE1P3132en
HVAC Products 9 Precontrol 23.04.2009
Heat demand signals from individual room controllers for air heating coils
Heat demand signals from primary air handling plant
A heat demand transformer converts the last 3 signals to a flow temperature setpoint.
In addition, 3 digital and/or 1 analog input can be configured on the controller as heat
request inputs.
Main menu > Commissioning > Extra configuration > Primary controller > Inputs
Operating line Range
Heat request modulating
Heating curve request 2-pos
DHW request 2-pos
Frost prot request 2-pos
From all request signals, the “Max” block (see illustration) generates the maximum
value. This maximum value is the flow temperature setpoint for the primary controller.
The setpoint is raised by the amount of the setpoint boost and send to a heat source or
another primary controller as “Heat demand of precontrol”.
9.5.1 Heat request modulating
A heat request can be preselected with a DC 0…10 V signal.
The signal can be matched to the DC 0…10 V signal source.
Main menu > Commissioning > Settings > … or
Main menu > Settings > Primary controller > Heat request
Operating line Range Factory setting
[Modulating] setpoint at 0 V –150…50 °C 0 °C
[Modulating] setpoint at 10 V 50…500 ° 100 °C
[Modulating] limit value 0…140 °C 10 °C
DC 0...10 V
02 46 810
-20
0
20
40
60
80
100
120
°C
2
3
3131D14
c
Value in °C at DC 0 V
d
Value in °C at DC 10 V
e
Limit value for heat demand (temperatures below this level are interpreted as “no heat demand”)
The DC 0…10 V input signal shall correspond to a flow temperature setpoint range of
20…120 °C. The following parameter settings are required:
[Matching] setpoint at 0 V: 20 °C
[Matching] setpoint at 10 V: 120 °C
Extra configuration
Example:

Table of Contents

Related product manuals