Main menu > Device information > Position 1 or 2 or 3
Operating line Remarks
Extension module Display of the module’s type reference
Software version Display of software version
Hardware version Display of hardware version
3.10 Leaving the password level
On completion of commissioning, select the user level (access level for the plant opera-
tor). To do this, proceed as follows:
1. After completion of commissioning, you reach the Main menu again.
2. Press the OK knob and the ESC button simultaneously.
3. The Access level menu appears.
4. Select the user level by turning the OK knob.
5. Confirm selection by pressing the OK knob.
3.11 Marking changes
If the internal standard application has been adapted or if, subsequently, submenu
Extra configuration has been accessed, an asterisk is placed in front of the plant type’s
type reference.
The asterisk denotes that the basic type was complemented by extra functions.
The asterisk is set automatically when leaving the Extra configuration menu, even if
nothing has been changed. In addition, on operating line ”Plant type adapted” of the
Device information menu, the value is set to ”Yes”.
The asterisk is deleted and line “Plant type adapted” shows the value as “No” if, on the
Basic configuration menu, the old or a new standard application is loaded for the plant
type. A new configuration is made based on the selected application.
Marking
Resetting the marking