176/232
Building Technologies Boiler Sequence Controller RMK770 CE1P3132en
HVAC Products 10 Heating circuit control 23.04.2009
Setting --- deactivates the function.
t
t
2522D07
T
Vw
T
Vw
Maximum boost =
ΔT
Vw
/ Δt
t Time
Δt Unit of time
TVw Flow temperature setpoint
ΔTVw Rate of setpoint boost per unit of time
Main menu > Commissioning > Settings > … or
Main menu > Settings > Heating circuit > Limitations
Operating line Range Factory setting
Flow temp rise max ---- (none) / 1…600 K/h ----
Flow temperature max
0…140 °C 80 °C
Flow temperature min
---- (none) / 0…140 °C ----
Frost protection for the plant Off / On On
10.8.5 Pump overrun and mixing valve overrun
To protect the boiler against overtemperatures after the burner has shut down, a con-
sumer overrun time can be set on the boiler controller.
10.8.6 Pump kick and valve kick
The pump kick is a protective function that is carried out periodically. It prevents pumps
and/or mixing valves from seizing after longer off periods.
10.9 Heat demand
The internal heating circuit can be connected either directly to the main header (heat
distribution zone) or downstream from the primary controller (heat distribution zone on
the consumer side if a primary controller is present).
This can be parameterized with the following setting:
Main menu > Commissioning > Extra configuration > Heating circuit
> Heat req heat circ
Operating line Range Factory setting
Heat req heat circuit acting on Main distributor /
Primary controller
Main distributor
Settings