15 Fault tracing support
If a fault is displayed, it is always practical to select the Main menu, operating line ”Faults
> Faults current”
, and look for any pending fault status messages before starting to
rectify a fault. If an extension module is faulty, that fault must be corrected first because
it can lead to sub sequential fault status messages.
For a detailed description of the display, acknowledgement and resetting of faults, refer
to subsection 13.5.1 “Acknowledgement and reset“.
15.1 Fault code list
The RMK770 controller has maximum 1 heating circuit and 1 time switch. Index 1
indicates that the fault occurred on this plant.
The table below contains the fault number texts with which the controller is supplied.
Texts with designations of aggregates, such as [Boiler …], [Primary controller] and
[Heating circuit], can be changed on the password level.
Number Name (as supplied) For explanation, refer to section …
10
Outside temp sensor error
10.11
11
>1 outside temperature sensor
10.11
12
Outs sensor simulation active
10.11
50 [HC 1] error flow sensor 10.11
51 [HC 1] error return sensor 10.11
57
Prim controller error flow sensor
9.10
58
Prim controller error ret sensor
9.10
60
Room sensor error plant 1
10.11
61
>2 room sensors in plant 1
10.11
301 [Boiler 1] boiler sensor error 7.15
302 [Boiler 2] boiler sensor error 7.15
303 [Boiler 3] boiler sensor error 7.15
304 [Boiler 4] boiler sensor error 7.15
305 [Boiler 5] boiler sensor error 7.15
306 [Boiler 6] boiler sensor error 7.15
311 [Boiler 1] return sensor error 7.15
312 [Boiler 2] return sensor error 7.15
313 [Boiler 3] return sensor error 7.15
314 [Boiler 4] return sensor error 7.15
315 [Boiler 5] return sensor error 7.15
316 [Boiler 6] return sensor error 7.15
321 [B1] flue gas temp sensor error 7.15
322 [B2] flue gas temp sensor error 7.15
323 [B3] Flue gas temp sensor error 7.15
324 [B4] flue gas temp sensor error 7.15
325 [B5] flue gas temp sensor error 7.15
326 [B6] flue gas temp sensor error 7.15
330
Main flow sensor error
6.4
331
Main return sensor error
6.4
332
[Boiler seq] MBRT sensor error
6.4
333
Consumer return sensor error
6.4
2202 Main contr h’request mod error 6.8
2203 Prim contr h’request mod error 9.10
2300 >1 boiler faulty 6.8
2301 [B1 burner] fault 7.15
Note