40/232
Building Technologies Boiler Sequence Controller RMK770 CE1P3132en
HVAC Products 3 Commissioning 23.04.2009
Main menu > Commissioning > Extra configuration > Primary controller > Outputs
Operating line Range Name
Mixing valve 3-pos PrCtrVlvMx
Mixing valve modulating PrCtrVlvMx
System pump RMK770…, RMZ7…* TPu_A
System pump B TPu_B
* Here, the free outputs are available for selection
Flow temperature sensor in the primary controller loop.
Return temperature sensor in the primary controller loop.
System pump A (the menu item does not show designation ”A”).
System pump B, if the system pump is a twin pump.
3-position or modulating mixing valve for precontrol.
For more detailed information, refer to chapter 9 “Precontrol”.
3.4.4 Hydraulics-dependent inputs and outputs of function
block “Heating circuit“
T
T
TRtCo
TRtMn
T
TMnFl
T
T
T
PrCtrVlvMx
TRtPrCtr
TFlPrCtr
TPu_A
T
T
T
TRtHCtr
TFlHCtr
HCtrPu_
T
T
T
TFlHCtr
HCtrVlvMx
TRtHCtr
HCtrVlvMx
HCtrPu_
T
TPu_B
HCtrPu_B
HCtrPu_B
T
Main menu > Commissioning > Extra configuration > Heating circuit
Operating line Range Factory setting
Heat req heat circuit acting on Main distributor / Primary
controller
Main distributor
Main menu > Commissioning > Extra configuration > Heating circuit > Inputs
Operating line Range Name
Flow sensor
RMK770…, RMZ7…* TFlHCtr
Room sensor Tr
Return sensor
Special day input
Holiday input
* Here, the free inputs are available for selection
Flow sensor (TFlPrCtr)
Return sensor (TRtPrCtr)
System pump A (TPu_A)
System pump B (TPu_B)
Mixing valve
(PrCtrVlVMx)