167/232
Building Technologies Boiler sequence controller RMK770 CE1P3132en
HVAC Products 10 Heating circuit control 23.04.2009
3131B20
TOeff
+
-
SpTR
TR
20 °C
SpTFlDe
SpTFlHi
SpTRN
TFl
TOeff
TODe TOHi
+
-
+
-
+
+
TFl
SpTR
TR × V
-
Due to the room temperature deviation ΔTV, the change of flow temperature setpoint
corresponds roughly to the value of:
ΔTFl=ΔTR × V × (sHc + 1)
ΔTFl Flow temperature setpoint change sHc Heating curve slope
ΔTR Room temperature setpoint change Sp Setpoint
V Room influence TRx Room temperature
During boost heating, the room temperature setpoint boost also produces an increase
of the flow temperature setpoint. In that case, the greatest of the 2 values is used for
generating the setpoint.
3131B22
SpTR
TR
+
-
TR
TR × V
-
TRBoost
MAX TReff
The resultant room temperature setpoint has a minimum limitation at 5 °C and a maxi-
mum limitation at 35 °C.
10.5.4 Heating limit switch
The heating limit switch can restrict the amount of heat delivered to the heating circuit.
This prevents the waste of heating energy at higher outside temperatures.
To determine the heating limit, the following outside temperature values are taken into
consideration (refer to subsection 10.5.1 “The composite and the attenuated outside
temperature”):
• The current outside temperature TO
• The composite outside temperature Toeff
• The attenuated outside temperature TostrDmp
Main menu > Commissioning > Settings > … or
Main menu > Settings > Heating circuit > Space heating
Operating line Range Factory setting
Comfort heating limit ---- / –5…25 °C 17 °C
Economy heating limit ---- / –5…25 °C 5 °C
Heat limit with Comfort preset Inactive / Active Inactive
Note the following:
• When the Comfort heating limit is set to “----“ (no heating limit), a heating limit only
applies to Economy
and Protection mode. And there is no changeover to sum-
mer operation
• When the Economy heating limit is set to “----“ (no heating limit), the Comfort heating
limit takes effect in Economy
and Protection mode
Rule of thumb
Settings