Building Technologies Boiler Sequence Controller RMK770 CE1P3132en
HVAC Products 13 Function block “Faults“ 23.04.2009
13.9 Communication
When communication is activated, the impact on fault handling is as follows:
Fault status messages are always delivered via bus and can be further handled by
other Synco™ 700 devices
Fault status messages from other Synco™ 700 devices are shown on the controller
Fault status messages from other Synco™ 700 devices can be delivered to a fault
relay
Fault status messages can be acknowledged from a remote location (e.g. from the
operator station using the OCI700.1 service tool).
It can be selected whether fault status messages with self-holding may also be reset
from a remote location or whether the self-holding reset must always be made locally.
Main menu > Commissioning > Communication > Basic settings
Operating line Range Factory setting
Remote reset of fault No / Yes No
A controller cannot acknowledge any fault status messages on other controllers.
13.10 Fault relays
To forward fault status messages, or to indicate them optically or audibly on a control
panel, for instance, 2 fault status outputs “Fault relay 1“ and “Fault relay 2“ of the
function block can be configured to any 2 free outputs N.Q…
Main menu > Commissioning > Extra configuration > Faults > Outputs
Operating line Adjustable values / display / remarks
Fault relay 1 --- / N.Q1 (free relays only) /
Assignment of fault relay
Fault relay 2 --- / N.Q1 (free relays only) /
Assignment of fault relay
For each of the 2 fault relays, the following settings can be made:
Fault priority:
Priority at which the relay shall be energized
Signalling:
The following signalling variants can be selected:
Internal fault (optically): The fault relay only signals internal faults and remains
energized until faults are no longer pending
Internal fault (audibly): The fault relay only signals internal faults and remains en-
ergized until the fault is acknowledged
Fault via bus (audibly): The fault relay only signals from the bus and remains en-
ergized until the fault is acknowledged
Inversion:
No means that the relay is energized should a fault occur
Yes means that the relay is deenergized should a fault occur
Setting values