190/232
Building Technologies Boiler Sequence Controller RMK770 CE1P3132en
HVAC Products 12 Function block “Miscellaneous“ 23.04.2009
12 Function block “Miscellaneous“
12.1 Overview of function block
Display 1
Display 2
Display 4
Miscellaneous
12.2 Configuration
Function block “Miscellaneous” is automatically provided for all basic types. To activate
the function block, special basic configuration is not required.
The functions required for the plants can be activated in the extra configuration.
Main menu > Commissioning > Extra configuration > Miscellaneous > Inputs
Operating line Adjustable values / remarks
Outside temperature
Display input 1
Display input 2
Display input 3
Display input 4
Main menu > Commissioning > Extra configuration > Miscellaneous > Outputs
Operating line Adjustable values / remarks
Outside temperature relay
Main menu > Commissioning > Extra configuration > Miscellaneous
Operating line Range Factory setting
Business card Yes / No Yes
Activation of the business card is described in section 4.5.4 „Electronic business card“.
12.3 Outside sensor
An outside sensor can be connected to the RMK770.
It can be used for the following
purposes:
• Compensating variable for the heating circuit
• Compensating variable for the heat demand transformers
• For certain frost protection functions
• For locking the boilers as a function of the outside temperature
Extra configuration
Inputs
Outputs
Functions
Business card