Building Technologies Boiler sequence controller RMK770 CE1P3132en
HVAC Products 16 Addendum 23.04.2009
16.2.5 Faults
Main menu > Settings > Faults > Fault input 1 (or 2, 3 or 4)
Datapoint name Factory setting
Fault text 1: [Fault input 1] fault
Fault text 2: [Fault input 2] fault
Fault text 3: [Fault input 3] fault
Fault text 4: [Fault input 4] fault
16.2.6 Meters
Main menu > Settings > Data acquisition > Meter 1 (or 2, 3 or 4)
Datapoint name Factory setting
Meter 1: Meter 1
Meter 2: Meter 2
Meter 3: Meter 3
Meter 4: Meter 4
16.2.7 Devices
Main menu > Settings > Texts
Datapoint name Factory setting
Device name: Dv name
File name: File name
Display input 1: Display input 1
Display input 2: Display input 2
Display input 3: Display input 3
Display input 4: Display input 4
Business card line 1: Business card line 1
Business card line 2: Business card line 2
Business card line 3: Business card line 3
Business card line 4: Business card line 4
16.2.8 Menu tree
On the software side, all setting and readout values are arranged as data points (oper-
ating lines) of the menu tree.
Using the operating elements of the operator unit, every operating line can be selected,
displayed or set in accordance with the access right.
The
Main menu is subdivided into 18 submenus: The display depends on the products
used and the type of plant:
1. Commissioning 10. Heating circuit
2. Boiler sequence manager 11. Data acquisition
3. Boiler 1 12. Miscellaneous
4. Boiler 2 13. Time of day/date
5. Boiler 3 14. Faults
6. Boiler 4 15. Settings
7. Boiler 5 16. Device information
8. Boiler 6 17. Data backup
9. Primary controller