193/232
Building Technologies Boiler sequence controller RMK770 CE1P3132en
HVAC Products 12 Function block “Miscellaneous“ 23.04.2009
12.4 Display inputs
On the RMK770, 4 universal inputs can be defined for display purposes.
Main menu > Commissioning > Extra configuration > Miscellaneous > Inputs
Operating line Adjustable values / remarks
Display input 1 Assign terminal
Display input 2 Assign terminal
Display input 3 Assign terminal
Display input 4 Assign terminal
The type or unit of the display input can be selected with the input identifier.
Main menu > Commissioning > Extra configuration > Miscellaneous > Input identifier
Operating line Range Factory setting
Display input 1 °C / % / g/kg / kJ/kg /
W/m2 / m/s / bar / mbar
/ Pa / ppm / Universal
000.0 / Universal 0000 /
Digital
°C
Display input 2 Like display input 1 °C
Display input 3 Like display input 1 °C
Display input 4 Like display input 1 °C
For detailed information about resolution, type of sensor, etc., refer to subsection 3.4.7
“Configuration of the universal inputs and outputs”.
The type of input can be selected. In the case of an analog input, it is the type of input,
and in the case of a digital input, the normal position.
Main menu > Commissioning > Settings > … or
Main menu > Settings > Inputs > …X…
Operating line Range Factory setting
Type reference Ni1000 / 2×Ni1000 / T1
/ Pt1000 / 0…10 V
Ni1000
Value low Depending on the
selected type
Depending on
the type
Value high Depending on the
selected type
Depending on
the type
Correction
–3.0…+3.0 K 0.0 K
Normal position Open / Closed Open
The inputs can be assigned free text (maximum 20 characters).
Main menu > Commissioning > Settings > … or
Main menu > Settings > Texts
Operating line Range Factory setting
Display input 1
Max. 20 characters
Display input 2 Same as display input 1
Display input 3 Same as display input 1
Display input 4 Same as display input 1
For more detailed information about the configuration of analog inputs, please refer to