Building Technologies Boiler Sequence Controller RMK770 CE1P3132en
HVAC Products 8 Heat demand and heat requests 23.04.2009
The heat demand transformer converts the position heat request signals (in %) to heat
demand signals with a flow temperature setpoint.
The following example of an air handling plant shows this.
T
T
T
T
RMH760
3131B05
Room unit
(in reference room)
Central
air handling
DHW
precontrol
Chilled water
precontrol
Air supply area
RMH760
RMU...
0...100 %
3131B06
Precontrol
heating
Ventilation
Precontrol
refrigeration
Heat demand
transformer
Refrigeration
demand
transformer
Based on the valve position of the air handling plant(s), the heat demand transformers
calculate a flow temperature setpoint.
If an outside temperature signal is available on the primary controller, the flow tempera-
ture setpoint according to the heating curve is used as a start value. If there is no
outside temperature signal, the flow temperature at curvepoint 1 is used as the stat
value.
This flow temperature start value is matched to the actual heat demand in a way that
the heat consumer with the greatest heat demand has a valve position of 90%.
If the valve position is >90%, the flow temperature is increased
If the valve position is <90%, the flow temperature is decreased
The maximum flow temperature readjustment can be parameterized.
To ensure that minimum opening travel of the valve does not produce a demand for
heat, a switch-off threshold can be defined.
Demand for heat is computed only if the valve positions exceed “Threshold on”
If the valve positions of all consumers are below “Threshold off“, the demand for heat
is suppressed again
Main menu > Commissioning > Settings > … or
Main menu > Settings > Boiler sequence manager > Demand control
Main menu > Settings > Primary controller > Demand control
Operating line Range Factory setting
[Curvepoint 1] outside temp –50…50 °C –10 °C
[Curvepoint 1] flow temp 0…140 °C 70 °C
[Curvepoint 2] outside temp –50…50 °C 20 °C
[Curvepoint 2] flow temp 0…140 °C 70 °C
Flow temp correction max 0…100 K 10 K
Control action Slow / Medium / Fast Medium
Request evaluation Maximum / Average Maximum
Limit value request on
(Threshold off)…100%
10 %
Limit value request off 0…(threshold on)
5 %
Example:
A
ir handling plant