Building Technologies Boiler Sequence Controller RMK770 CE1P3132en
HVAC Products 13 Function block “Faults“ 23.04.2009
Main menu > Commissioning > Settings > … or
Main menu > Settings > Inputs > RMK770.D… (or RMZ78…)
Operating line Range Factory setting
Normal position Open / Closed Open
Following can be set for each fault status message:
Main menu > Commissioning > Settings > … or
Main menu > Settings > Faults > Fault input 1 (or 2, 3 or 4)
Operating line Range Factory setting
Fault text Max. 20 characters [Fault input 1]
Fault*
Fault status signal delay
00.00…59.55 m.s 00.05 m.s
Fault acknowledgement
None / Acknowledge /
Acknowledge and reset
None
Fault priority Urgent / Nonurgent Nonurgent
Impact of fault No stop / Stop Stop
Limit value fault on
0 / 1** 1
Limit value fault off
0 / 1** 0
* Or fault input 2, 3 or 4
** Depending on the “Input identifier”
These settings can be made only if the relevant input has previously been activated in
the extra configuration.
For more detailed information, refer to section 13.5 ”Fault properties“.
The text for the universal fault inputs is predefined via
[Fault input 1]Fault through
[Fault input 4]Fault. The texts can be adapted.
Signal at the
fault input
Fault status
message
3131D31
Signal delay
The fault status signal delay is used to set the period of time a fault must be pending to
be handled as such.
When parameterized “Stop“ at the universal fault inputs, the controller switches off all
function blocks (boiler sequence manager, all boilers, primary controller, and the heat-
ing circuit). Frost protection continues to be active.
Number Text Effect
9000 >1 fault input fault
Urgent message; must not be acknowl-
edged (effect at each fault input can be
selected)
9001 [Fault input 1] fault * Effect according to settings
9002 [Fault input 2] fault * Effect according to settings
9003 [Fault input 3] fault * Effect according to settings
9004 [Fault input 4] fault * Effect according to settings
* Factory setting; text is editable
Fault text
Fault status
signal delay
Fault effect
Fault status messages