Building Technologies Boiler sequence controller RMK770 CE1P3132en
HVAC Products 3 Commissioning 23.04.2009
The plant type is made up of a 2-digit number, e.g. K2.3:
The first digit defines the type of hydraulic circuit of the boiler sequence
The second digit defines the type of burner or the type of burner control:
Kx.1: 1-stage burner
Kx.2: 2-stage burner
Kx.3: Modulating burner with 3-position control
For DC 0…10 V control of a modulating burner, the 1-stage burner is used as the
basic stage. In addition, a DC 0…10 V output must be assigned in the extra configu-
ration
The plant type always applies to a boiler sequence
with 2 boilers
and using the same type of burner
Additional boilers, other types of burner, a heating circuit or a primary controller can
be configured in the extra configuration.
The plant type activates function block “Boiler sequence manager“ and function
blocks “Boiler 1” and “Boiler 2”
K
Basic type K; no preconfigured inputs and outputs
K1.x
3132S01
K2.x
3132S04
M M
K3.x
3132S07
M M
Plant type
Types of hydraulic circuit